ANALISIS PENGUJIAN PROTEKSI SALURAN TRANSMISI MENGGUNAKAN DISTANCE RELAY PADA BAY LINE SENGKOL–KUTA DI GI 150 KV SENGKOL

Authors : Haris Setyo Adi; Agung Budi Muljono
article cite 0 Year 2025
source: Jurnal Informatika dan Teknik Elektro Terapan
Abstract

Distance relay is a crucial component in the protection system of high-voltage transmission lines. Faults on transmission lines can cause equipment damage and disrupt the continuity of power supply. This study aims to evaluate the performance and characteristics of the distance relay on the Sengkol–Kuta transmission line bay at the 150 kV Sengkol Substation. The testing method employed is shutdown testing, referring to IEC 60255-121:2014 and SPLN No.15 of 2014 standards. The test was conducted using an Omicron CMC 356 test set and Test Universe software. The protection zones examined include zone-1 and zone-2, with impedance and operating time parameters adjusted according to the line length. The results indicate that the MiCOM P543 relay operates accurately and responsively to simulated faults, as demonstrated by Mho and Quadrilateral characteristic curves that align with the protection system boundaries. These findings confirm that the implemented distance relay protection system functions optimally in fault detection and contributes to maintaining the reliability of the power system.


Concepts :
Power Systems Fault Detection
Electrical Fault Detection and Protection
Engineering and Technology Innovations
article cite 0 Year 2025 source Jurnal Informatika dan Teknik Elektro Terapan
Citations by Year
YearCount
2025 0